What this covers
- Transient stability — generator rotor angle and machine synchronism following faults and switching events.
- Critical clearing time — the maximum fault duration the system can survive, which feeds directly back into protection settings.
- Voltage stability — recovery behaviour and the risk of voltage collapse under heavy loading.
- Motor reacceleration — whether motor loads recover after a fault or stall and must be shed.
- Islanding and load shedding — behaviour on separation from the grid, and the load shedding scheme needed to survive it.
- Frequency response — governor and generator response to load and generation imbalance.
What you receive
- Stability study report covering each contingency assessed
- Time-domain simulation results for rotor angle, voltage and frequency
- Critical clearing times with protection implications identified
- Load shedding scheme recommendations where required
Standards and references
Analysis references IEEE 399 and IEEE 1110 for machine modelling, with acceptance criteria taken from the project specification and applicable grid code.
Related services
Load Flow Analysis
Steady-state studies of voltage profile, power distribution and loading across the network.
Short Circuit Analysis
Fault current calculations to verify equipment ratings and underpin protection coordination.
Arc Flash Studies
Incident energy analysis and PPE categories to protect people working on live equipment.
Need power system stability analysis scoped?
Work directly with the engineers doing the analysis — clear scoping from the first conversation.
Get in Touch